APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Input Status
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: INPUTS
PIC 5 PATH: Main Menu Input Status
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Compressor Start Contact STAR_AUX OPEN/CLOSE RO
2 Compressor Run Contact RUN_AUX OPEN/CLOSE RO
3 Damper Valve Fully Closed DMP_FC NO/YES RO
4 Damper Valve Fully Opened DMP_FO NO/YES RO
5 Damper Valve Status DMP_ACT 0 to 3 RO
6 0=Closed, 1=Interim, 2=Opened
3=Failure
7 HGBP Valve Fully Closed HGBP_FC NO/YES RO
8 HGBO Valve Fully Opened HGBP_FO NO/YES RO
9 HGBP Valve Status HGBP_ACT 0 to 3 RO
10 0=Closed, 1=Interim, 2=Opened
3=Failure
11 High Pressure Switch HP_SW OPEN/CLOSE RO
12 Remote Contact REM_CON OPEN/CLOSE RO
13 Emergency Stop Contact E_STOP OPEN/CLOSE RO
14 Ice Build Contact ICE_CON OPEN/CLOSE RO
15 Chiller Lockout REM_LOCK OPEN/CLOSE RO
16 Spare Safety Input SAFETY OPEN/CLOSE RO
17 Starter Fault Feedback STARTFLT OPEN/CLOSE RO
18 Fire Security Interlock FS_LOCK OPEN/CLOSE RO
19 Guide Vane 1 Actual Ohms GV1_OHMS
ohms
RO
20 Guide Vane 1 Actual Pos GV1_ACT
%
RO
21 VFD Actual Speed VFD_ACT
%
RO
22 Diffuser Actual Pos DIFF_ACT
%
RO
23 Auto Demand Limit Input AUTO_DEM
mA
RO
24 Auto Water Temp Reset AUTO_RES
mA
RO
25 Refrig Leak Sensor REF_LEAK
mA
RO
26 Evap Flow Input EVAPFLIN
mA
RO
27 Cond Flow Input CONDFLIN
mA
RO
28 VFD Speed Feedback VFD_IN
V
RO
29 Guide Vane 1 Act Input GV1_MA
mA
RO
30 VFD Current Act Input VFDC_MA
mA
RO
31 ISM Trip Relay Status TRIPR OPEN/CLOSE RO
32 BACnet Dongle bacdongl NO/YES RO
RO Read Only